[article-header.htm]

What’s Wrong With This Picture?

Lead-acid Batteries in Buildings
Number 3 in a Series
2x2 black.jpg (633 bytes)
This is a picture of batteries used to start standby generators in a telephone company central office. The generators associated with these starting batteries total over five megawatts of ac power generation capacity.

There are three 24 Volt starting plants, each utilizing four battery six cell monoblocs in which two batteries are connected in series and then paralleled with another series connected set. The battery wiring connections are made at the top of the battery rack on buss bars held in place by the red insulators. There are six loads with each load being fed through a separate steel conduit.

The battery hazardous materials inventory in this fire control area far exceeds the exemption amounts permitted by the local building and fire codes (Uniform).
Looking at the picture we see the following:
  • The flooded or wet cell batteries being used appear to be the type used in trucks and earth moving equipment. The batteries bear the Caterpillar® Model 9G4231 flooded cell part number. To the best of our understanding, the oxygen index rating of the case material is not high enough to be flame self extinguishing (fire retardant) rated nor are the vent caps of a flash (spark) arrester type. Batteries for use in facilities have specific requirements of which this truck type battery does not qualify.

  • The battery to load feeder has no provisions for overcurrent protection or disconnection means. While it might be argued that no overcurrent protection or disconnection means is required when the feeder length is a few feet, the shortest run in this grounded system feeder is well over 30 feet. Both conductors are in the same steel conduit.

  • This installation lacks the spill control provisions (4 inch liquid-tight barrier etc.) required in both the building and fire codes. Also, without a spill management system, it is incredible that a reasonable and prudent Emergency Management Plan is in place.

An inspection of the battery shown in the battery monobloc picture indicates improper maintenance procedures where battery acid appears to be running from the terminal post area and down the side of the battery. 

Since this acid film conducts electricity and the system is grounded, a battery fire can (and does) occur due to the shorting of the battery to the grounded battery rack. 

When one encounters what appears to be hydrometer spillage such as this, the whole maintenance procedure and quality control over the process immediately becomes suspect.

2x2 black.jpg (633 bytes)
Robert L. Taylor, President
Morning Star Industries, Incorporated
Power Systems Solutions Division
304 Lake Terrace
Rockwall, Texas 75087
Tel: 972-618-9630 
  Fax: 775-806-4124
Email: msi@msi.nu
[article-footer.htm]